heavy cable tray, not perforated, head shape suitable for positive locking covers, certified including electrical conductivity according to DIN EN 61537/VDE 0639
data sheet Assembly Instruction Do not walk upon!
Continously hot galvanized (Sendzimir process) (DIN EN 10346)
height | width | length | t material thickness | A cross section area | QSKdistributed load control cable | weight | ||
---|---|---|---|---|---|---|---|---|
RS 60-10S | 60 mm | 100 mm | 3000 mm | 1,50 mm | 57 cm² | 0,09 kN/m | 9,00 kg | |
RS 60-20S | 60 mm | 200 mm | 3000 mm | 1,50 mm | 117 cm² | 0,18 kN/m | 12,60 kg | |
RS 60-30S | 60 mm | 300 mm | 3000 mm | 1,50 mm | 177 cm² | 0,27 kN/m | 16,10 kg | |
RS 60-40S | 60 mm | 400 mm | 3000 mm | 1,50 mm | 237 cm² | 0,36 kN/m | 19,60 kg | |
RS 60-50S | 60 mm | 500 mm | 3000 mm | 1,50 mm | 297 cm² | 0,45 kN/m | 23,20 kg | |
RS 60-60S | 60 mm | 600 mm | 3000 mm | 1,50 mm | 357 cm² | 0,54 kN/m | 26,70 kg |
Hot-dip galvanized, according to BS 729 (DIN EN ISO 1461)
height | width | length | t material thickness | A cross section area | QSKdistributed load control cable | weight | ||
---|---|---|---|---|---|---|---|---|
RS 60-10F | 60 mm | 100 mm | 3000 mm | 1,50 mm | 57 cm² | 0,09 kN/m | 9,60 kg | |
RS 60-20F | 60 mm | 200 mm | 3000 mm | 1,50 mm | 117 cm² | 0,18 kN/m | 13,30 kg | |
RS 60-30F | 60 mm | 300 mm | 3000 mm | 1,50 mm | 177 cm² | 0,27 kN/m | 17,10 kg | |
RS 60-40F | 60 mm | 400 mm | 3000 mm | 1,50 mm | 237 cm² | 0,36 kN/m | 20,80 kg | |
RS 60-50F | 60 mm | 500 mm | 3000 mm | 1,50 mm | 297 cm² | 0,45 kN/m | 24,60 kg | |
RS 60-60F | 60 mm | 600 mm | 3000 mm | 1,50 mm | 357 cm² | 0,54 kN/m | 28,30 kg |